CERAMIN - manual (EN)

Welcome to interactive presentation, created with Publuu. Enjoy the reading!

41

The overlap of sealing tape and

sealing tape or sealing tape and

inner or outer corner must be at

least 5 cm.

The sealing tapes in the wall/

floor connection are applied by

spreading the CLASSEN Multi-

connect adhesive over the entire

surface to above the edge of the

membrane using a B3 toothed

spreader in accordance with the

manufacturer’s instructions.

Completed area must be inspe-

cted for defects or damage

(e.g. perforations).

Leaky or unclean areas must be

cient tightness is ensured.

The membranes are then bonded

over the entire surface. Firm

pressing guarantees full-surface

bonding. Air bubble entrapment

must be avoided by pressing on

and carefully spreading out with

a smoothening spatula.

ATTENTION: Waterproofing membranes, sealing tapes as

well as system components must be carefully processed

with new sharp tools. These sealing components must not

be damaged in the process, as this would lead to leaks.

The waterproofing is complete when it is fully bonded to all

surfaces.

TIP: Residual and

waste material can

be disposed of prop-

erly in the residual

waste.

5 cm

5 cm

WATERPROOFING ACCORDING TO DIN 18534

suitably reworked, so that suff-